GoodWe inverter error code 10
GoodWe uses code 10 in more than one product range, and it doesn't always mean the same thing. Check which range your inverter belongs to below.
WattMate is not affiliated with GoodWe. This page summarises GoodWe's own published documentation; your installer and GoodWe are the authority on your system. WattMate doesn't repair systems or make site visits.
As documented for Sbp G2
- Meaning
- LVRT Undervoltage
- Likely cause
- Utility grid exception. The duration of the utility grid exception exceeds the set time of LVRT.
- What the manual says to do
- If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. If the problem occurs frequently, check whether the grid frequency is within the permissible range or contact the local power company.
- Manufacturer's severity
- Critical
GoodWe's documentation says this one needs your installer.
Extracted from GoodWe's published manual. Check it against the manual for your model. Open the source document
As documented for Sdt G2
- Meaning
- A Fan Fail
- Likely cause
- A fault occurs in all fans of the inverter.
- What the manual says to do
- Restart the inverter and check whether the inverter can work normally.
- Manufacturer's severity
- Warning
GoodWe's documentation says this one needs your installer.
Extracted from GoodWe's published manual. Check it against the manual for your model. Open the source document
When to call your installer or the warranty line
Your installer is your first warranty contact. If they've gone, the manufacturer's warranty line still covers the hardware. Don't open the inverter or battery case yourself: work inside it is for a licensed electrician.
If you see smoke, scorch marks or smell burning, switch the system off at the AC and PV isolators and call your installer. If anyone is in danger, call 000.